Field Loss in Power Transformer (T.E.A.M. Problem 21a)

Transformers with MagNet

Shielding can be used to substantially reduce magnetic field strengths outside of a transformer. Considerations, such as its electric properties and geometry, are needed to determine the type of shielding required.

Presented here is MagNet's analysis of the second set of configurations from the family of benchmarks involving two exciting coils directed in opposite directions and shielded by a non-magnetic steel plate. The steel plate has four configurations; no slot, one slot, two slots and three slots. The eddy current losses are compared in all configurations to measured results. By taking advantage of symmetry present in the geometry, only a quarter of the model can be modelled which decreases the time required to complete the simulation.

The following is based on the Testing Electromagnetic Analysis Methods (T.E.A.M.) Problem #21: 3-D Stray Field Loss Model: Benchmark Family. The benchmark can be found on the International Compumag Society's website.

TEAM-based benchmark family: Problem 21a Field Loss in Power Transformer

METHODS and RESULTS

CURRENT DENSITY PLOTS of the INDUCED EDDY CURRENTS

Since the sources powering the transformer are sinusoidal, MagNet's Time Harmonic 3D solver can be used to simulate this model. Shown here are snapshots of shaded current density plots of the induced eddy currents in the four steel plate configurations.

View larger image

OHMIC LOSS FIELD PLOTS

Along with shaded current density plots MagNet's post-processor also automatically computes ohmic loss fields. Shown here are snapshots of the shaded ohmic loss field plot for the four steel plate configurations.

View larger image

GRAPHICAL COMPARISONS of POWER LOSSES

The integral of the ohmic loss field in MagNet is used to compare to the measured eddy current model of TEAM Problem 21a. Shown here is a graphical comparison of power losses for the four steel plate configurations.

View larger image

GRAPHICAL COMPARISON between MAGNET and the MEASURED RESULTS

In addition to measured power loss values, TEAM Problem 21a also presents measured magnetic flux densities along contours off of the surface of the steel plate for configuration 21a-2. Shown here is a graphical comparison between MagNet and the measured results along the two contours.

View larger image